CLRB: Repeat Cycle Plug-In Timer
• Independent On & Off
Adjustments
• Digital CMOS Design
• 10 Amp, DPDT
• ±0.2% Repeatability
• Transient Protected
• On Time Ranges Up to
24 Hours
• Off Time Ranges Up to
24 Hours
Operation
Repeat Cycle
When input voltage is applied to the CLRB, the first delay period (off time) begins. At the end of the off time period, the internal relay is energized and the second delay period (on time) begins. At the end of the on time, the internal relay is de-energized. The CLRB will continue to cycle the internal relay until the input voltage is removed. Separate knobs are used to adjust the off and on times. (The CLRB is also available with reverse operation.)
Specifications
Electrical
Input Voltage:
24 or 115VAC ±10%, 50/60Hz.
24 or 125VDC ±10%, Filtered to Full Wave.
Time Delays:
Type: Adjustable or Factory Fixed
Range: 50 Milliseconds to 24 Hours
Repeat Accuracy: ±0.2% of Time Range or
±10Milliseconds, whichever is Greater.
Fixed Time Accuracy: ±5% Worst Case
Reset Times: 50 Milliseconds,
Typical Protection: Varistor and/or R-C Network
Power Consumption: 5VA
Output Relay:
10 Amps @ 120/240VAC
500,000 Full Load Electrical Cycles
50,000,000 Mechanical Cycles
U.L. Ratings:
6.5 Amps, 1/3 HP, 125VA @ 240VAC
7 Amps, 1/6 HP, 125VA @ 120VAC
Physical
Mounting: Plug-In
Termination: 8 or 11 Pin & Blade Base
Packaging: Dust Cover
Weight: 7 Oz.
Ambient Temperatures
Operating: -10°C to 65°C
U.L. Operating: -10°C to 40°C
Storage: -10°C to 85°C