top of page

TUB: Universal Plug-In Timer

tub_edited.jpg

One Timer Does It All

 

Multiple Functions

 

Multiple Time Delays  

 

Digital CMOS Design

 

10 Amp, SPDT

 

±0.2% Repeatability

 

Transient Protected

 

Timing Ranges Up To 72 Minutes

Operation

Universal Timer

The e by the customer. The multiple function and time delay characteristics are selected by connecting jumpers to the TUB’s standard socket. The time delays range from .1 to 17 seconds up to 25 seconds to 72 minutes. A benefit is that you can easily program functions and time ranges, but someone else can’t change them by flipping a switch.

• On Delay
• Interval On

• One Shot

• Off Delay

• Repeat Cycle (First Cycle On or First Cycle Off)

 

Specifications

Electrical

Input Voltage:

     24 Volts, AC or DC, ±10%

     115 Volts, AC or DC, ±10%

Time Delays:

    Type: Adjustable

    Range: 100 Milliseconds to 72 Minutes in 4 ranges

    Repeat Accuracy: ±0.2% of Time Range or less

    Control Signal: 30 Milliseconds to insure turn-on

Reset Times:

    100 Milliseconds, Max.

    60 Milliseconds, Typical

Protection: Varistor and/or R-C Network

Power Consumption: 4VA

Output Relay:

    10Amp, SPDT 500,000 Full Load Cycles

    50,000,000 Mechanical Cycles

U.L. & cRUus Output Ratings:

     5 Amps, 1/3 HP, 125VA @ 240VAC

     5 Amps, 1/6 HP, 125VA @ 120VAC 

 

Physical

Mounting: Plug-In

Termination: 11 Pin or Blade Base

Packaging: Dust Cover

Weight: 7 Oz.

 

Ambient Temperatures

Operating: -10°C to 55°C

U.L. Operating: -10°C to 40°C

Storage: -10°C to 85°C

 

bottom of page