PVCO/L: Three Phase Voltage Relay  PVCO  PVCL

pvc_edited.jpg

10 Amp Relay

SPDT or DPDT

Undervoltage

Phase Loss (Single Phase)

Phase Imbalance

Phase Rotation

Pick-up & Drop-out Delays

Normal Condition LED

 

 

Operation

The PVC’s output contacts energize when:

1. All the phases are present;

2. The voltages are within 10% of the setting;

3. The phases are in the proper rotation

4. The phases are balanced;

5. The frequency is within tolerance.  Built into the PVC series is a 5 second pick-up delay to allow the three phase line to stabilize. If any of these conditions shift beyond the setpoints, the output contact will de-energize after a 5 second time delay.  Single phase conditions will be detected when the voltage in one phase is 5% different from the voltages in the other two phases (Phase Imbalance).

 

Specifications

Electrical

Line Voltage: 

110VAC to 600VAC, 3Ø

Frequency: 60Hz, 300 Series 50Hz

Line Voltage Ranges:

100 Series - 110VAC to 120VAC, 3Ø

200 Series - 208VAC to 240VAC, 3Ø

300 Series - 380VAC to 415VAC, 3Ø

400 Series - 440VAC to 480VAC, 3Ø

600 Series - 575VAC to 600VAC, 3Ø

Maximum Overvoltage:
10% of highest nominal voltage

Maximum Frequency Shift: 0.1Hz

Undervoltage: 10% below set point

Phase Imbalance: 5% typical

Phase Rotation: A - B - C

Phase Loss:
Complete loss to 95% of nominal

Time Delays:

Pick-up: 5 Sec. Fixed

Drop-out: 5 Sec. Fixed

Power Consumption: 16VA

Output Contacts: 

7 Amps @ 120VAC

5 Amps @ 240VAC

100,000 Full Load Electrical Cycles

10,000,000 Mechanical Cycles

 

Physical

Mounting: Surface

Termination: Screw Terminals

Packaging: Dust Cover

Weight: 8 Oz. Approx.

 

Ambient Temperatures

Operating: -20°C to 40°C

Storage:  -20°C to 85°C

 

 