MVPL: Multi-Range Three Phase Voltage Relay
1Ø & 3Ø Voltage
200 to 600VAC
Plug-In Package
Adj. Over & Under Voltage Trip
Phase Loss
Phase Rotation
Phase Imbalance
Adj. Re-Start Delay
Manual or Automatic Reset
Operation
The MVPL will monitor either 1Ø or 3Ø line voltage and provide a relay contact closure if all operating conditions are satisfied. Select the operating voltage from the top pot, set the percentage pot for 1Ø or 3Ø, and then apply the supply voltage. To change ranges, remove the supply voltage and re-apply.
The operating conditions include:
• Monitoring voltages within the adjustments:
• Range
• Over and Under percentage
• Three Phase:
• All phase present
• Proper phase rotation (A-B-C)
• Balanced phases
Automatic or Manual Reset is selected by the Restart pot. In Manual Reset when all conditions are correct, the manual reset button below the timing adjustment must be operated.
Specifications
Electrical
Line Voltage:
Single Phase: 200VAC to 240VAC, 1Ø
Three Phase: 200VAC to 600VAC, 3Ø
Supply Voltage:
24VAC, 120VAC or 240VAC, 1Ø, Continuous
Frequency: 50/60Hz
Nominal Voltage:
Adj. 200 to 600VAC *
Over/Under Voltage:
Adj. 8% to 14% of Selected Voltage
Phase Imbalance: 5%
Phase Rotation: A - B - C
Drop-out Delay: 2 sec. fixed
Re-Start Delay:
2 sec to 5 min., or manual reset
Power Consumption: 1.5VA
Output Rating @ 25°C:
10 Amps @ 125VAC
6 Amps @ 277VAC
1/8 HP @ 125, 277VAC
5 Amps @ 30VDC
Physical
Mounting: Plug-In
Termination: 8 Pin (Octal)
(Over 300VAC use OT-08)
Packaging: Dust Cover
Weight: 8.5 Oz. Approx.
Ambient Temperatures
Operating: 0°C to 65°C
Storage: -40°C to 85°C