top of page

MCS: On Delay Solid State Timer

mcs_edited_edited.jpg

• 1 Amp Output, 1NO

 

• Indicating LED

 

• Fixed or Adjustable Delays

 

• Screw Terminals or

  Push-On Tabs

 

• Voltages from 24

  to 240VAC

 

• Epoxy Filled

Operation

On Delay

When input power is applied to the MCS, the timing cycle begins. At the end of the timed period the load is energized. When input power is removed, the timing circuit is reset and the load is de-energized.

 

Specifications

Electrical

Input Voltage:

     24 to 240V, ±10%

Frequency:

     AC - 50/60Hz

     DC - Filtered to Full Wave

Time Delays:

     Type: Adjustable, Factory Fixed or Remote

     Range: 100 Milliseconds to 5 Minutes

     Repeat Accuracy: ±1% with Fixed Conditions

     Fixed Time Accuracy: ±20% worst Case

Reset Times:

     During Timing: 50 Milliseconds, Typical

     After Timing: 5 Milliseconds, Typical

Protection: Varistor and/or R-C Network

Power Consumption: 5VA

Output Ratings:

     Type: Solid State

     Form: One Normally Open (1NO, Form A) Non-Isolated

     Rating:

          1 Amp Continuous @ 25°C

          Resistive: 100%PF

          Inductive: 75-80%PF

          15 Amps Inrush, Non-repetitive

          30 mAmps to ensure Turn-on

Operations: 100,000 Cycles*

     * Cycles were selected to satisfy minimum testing at UL.

 

Physical Mounting: Ambient Temperatures Operating: 0°C to 65°C UL Operating: 0°C to 40°C Storage: -30°C to 85°C Notes: Remote Timing Resistors - multiples of 2.7 megohms will increase the time delay by 1 minute ±20%. For adjustment codes 3 & 4 a jumper or resistor must be installed across terminals 3 and 4 to allow the timer to time out.

 

Physical

Mounting: Surface, #6 Screws

Termination: Screw or .25” Push-On Tabs

Packaging: Epoxy Filled

Weight: 4 Oz.

 

Ambient Temperatures

Operating: 0°C to 65°C

UL Operating: 0°C to 40°C

Storage: -30°C to 85°C

 

Notes:

Remote Timing Resistors - multiples of 2.7 megohms will increase the time delay by 1 minute ±20%.

 

For adjustment codes 3 & 4 a jumper or resistor must be installed across terminals 3 and 4 to allow the timer to time out.

 