LLO/C: Dual Seal or Temp Stat Failure Relay LLO LLC
• Conductive or Float
Switch Inputs
• Dual Seal Failure
• Dual Temp Stat Failure
• 5K to 100KΩ Sensitivity,
Adjustable
• Low AC Sense Voltage
• Noise Filter
• Nusance Delay
Operation
Dual Seal or Temp Stat Failure
The LLO/C accepts inputs that are either conductivity (resistance) and/or normally closed temp-stat contacts. Internal logic circuitry determines the alarm condition. Seal Failure: Low reisitance sensed on either input Temp Stat Failure: Open contact on either input Diagnostic LEDs indicate the input generating the fault and output relay state.
Specifications
Electrical
Input Supply Voltage: 12, 24. 120 or 240 VAC, 10%
Frequency: 50/60Hz
Power Consumption: 2VA
Sensitivity Range: 5K to 100KΩ
Pick-Up/Drop-Out Delay: .5 Sec. Fixed
Max. Probe Voltage:
16 Volts AC Output Rating @ 25°C:
10 Amps @ 120VAC 5 Amps @ 250VAC, 30VDC
300W (D.C.), 1600VA (A.C.) Max. switching power (resistive)
100,000 Full Load Electrical Cycles
20,000,000 Mechanical Cycles
Indicators
2 Status LEDs: Inputs closed
1 Relay LED: Relay Energized
Physical
Mounting: Plug -In
Termination: 8 Pin Octal
Packaging: Dust Cover
Weight: 9 Oz.
Ambient Temperatures
Operating: 0°C to 40°C
Storage: -40°C to 85°C